Reference tables

2023 NEC

Conduit Fill Capacity Tables

Permitted fill percentages, conduit internal areas for EMT, PVC Schedule 40, and RMC, and conductor cross-sectional areas by insulation type.

Permitted fill

One conductor53%
Two conductors31%
More than two conductors40%

Conduit internal area (in²)

Trade sizeEMTPVC Sch 40RMC
1/2"0.3040.2850.314
3/4"0.5330.5080.549
1"0.8640.8320.887
1-1/4"1.4961.4531.526
1-1/2"2.0361.9862.071
2"3.3563.2913.408
2-1/2"5.8584.6954.866
3"8.8467.2687.499
3-1/2"11.5459.73710.01
4"14.75312.55412.882
Total internal cross-sectional area of each conduit type by trade size.

Conductor area (in²)

SizeTHHN / THWN-2XHHW-2THW
14 AWG0.00970.01390.0209
12 AWG0.01330.01810.026
10 AWG0.02110.02430.0333
8 AWG0.03660.04370.0556
6 AWG0.05070.0590.0726
4 AWG0.08240.08140.0973
3 AWG0.09730.09620.1134
2 AWG0.11580.11460.1333
1 AWG0.15620.15340.1901
1/0 AWG0.18550.18250.2223
2/0 AWG0.22230.2190.2624
3/0 AWG0.26790.26420.3117
4/0 AWG0.32370.31970.3718
250 kcmil0.3970.39040.4596
300 kcmil0.46080.45360.5281
350 kcmil0.52420.51660.5958
400 kcmil0.58630.57820.6619
500 kcmil0.70730.69840.7901
600 kcmil0.86760.87090.9729
700 kcmil0.98870.99231.101
750 kcmil1.04961.05321.1652
Approximate cross-sectional area of each insulated conductor, including insulation.

Source: NFPA 70, National Electrical Code, Chapter 9, Table 1; NFPA 70, National Electrical Code, Chapter 9, Table 4; NFPA 70, National Electrical Code, Chapter 9, Table 5. Published by NFPA.NEC 2023

Why two conductors get a lower limit than three

It looks like a typo but it isn't. Exactly two conductors in a round pipe can wedge against the wall on a bend — the jam ratio problem — while three or more bundle together and roll through. The tighter limit for two is a mechanical allowance, not a thermal one.

Fill and derating are the same problem

Both exist because bundled conductors cannot shed heat. Filling a conduit to the limit with current-carrying conductors will also trigger the bundling adjustment, reducing what each one carries. Passing the fill check does not mean the ampacity is unaffected.

Build a specific set in the conduit fill calculator, which handles mixed conductor sizes.