Reference tables · Conduit fill

RMC (rigid metal conduit)

3/4" RMC conduit fill capacity

3/4" RMC has an internal area of 0.549 in². At the 40% limit that applies to more than two conductors, it holds up to 16 12 AWG THHN conductors.

Capacity

Maximum conductors by size and insulation

ConductorTHHN / THWN-2XHHW-2THW
14 AWG221510
12 AWG16128
10 AWG1096
8 AWG653
6 AWG433
4 AWG221
3 AWG111
2 AWG111
1 AWG111
1/0 AWG111
2/0 AWG111
3/0 AWG11
Maximum number of same-size, same-insulation conductors in 3/4" RMC (0.549 in² internal). Counts above two use the 40% limit; a dash means not even one fits.

Fill limits

Internal area0.549 in²
One conductor53% — 0.2910 in²
Two conductors31% — 0.1702 in²
More than two40% — 0.2196 in²

Fitting is not the same as finishing

These counts are the mathematical fill limit, not a promise the pull will go well. A raceway at 39% fill with four 90° bends and a hundred feet between pull points is legal and miserable. Experienced installers routinely size up a trade size on long or bendy runs, and the material cost difference is usually smaller than the labour cost of a fight.

Two other things this table does not model. Nipples 24 inches and shorter between enclosures are permitted a much higher fill. And a mixed set of conductor sizes has to be summed by area rather than looked up by count — the conduit fill calculator handles that.

Remember also that conductor count drives ampacity derating separately. Filling this conduit with current-carrying conductors will reduce what each one can carry — see the bundling adjustment table.

Source: NFPA 70, National Electrical Code, Chapter 9, Table 1; NFPA 70, National Electrical Code, Chapter 9, Table 4; NFPA 70, National Electrical Code, Chapter 9, Table 5. Published by NFPA.NEC 2023

Related

Other sizes and types