RMC (rigid metal conduit)

3-1/2" RMC conduit fill capacity

3-1/2" RMC has an internal area of 10.01 in². At the 40% limit that applies to more than two conductors, it holds up to 301 12 AWG THHN conductors.

Capacity

Maximum conductors by size and insulation

ConductorTHHN / THWN-2XHHW-2THW
14 AWG400288191
12 AWG301221154
10 AWG189164120
8 AWG1099172
6 AWG786755
4 AWG484941
3 AWG414135
2 AWG343430
1 AWG252621
1/0 AWG212118
2/0 AWG181815
3/0 AWG141512
4/0 AWG121210
250 kcmil10108
300 kcmil887
350 kcmil776
400 kcmil666
500 kcmil555
600 kcmil444
700 kcmil443
750 kcmil333
Maximum number of same-size, same-insulation conductors in 3-1/2" RMC (10.01 in² internal). Counts above two use the 40% limit; a dash means not even one fits.

Fill limits

Internal area10.01 in²
One conductor53% — 5.3053 in²
Two conductors31% — 3.1031 in²
More than two40% — 4.0040 in²

Fitting is not the same as finishing

These counts are the mathematical fill limit, not a promise the pull will go well. A raceway at 39% fill with four 90° bends and a hundred feet between pull points is legal and miserable. Experienced installers routinely size up a trade size on long or bendy runs, and the material cost difference is usually smaller than the labour cost of a fight.

Two other things this table does not model. Nipples 24 inches and shorter between enclosures are permitted a much higher fill. And a mixed set of conductor sizes has to be summed by area rather than looked up by count — the conduit fill calculator handles that.

Remember also that conductor count drives ampacity derating separately. Filling this conduit with current-carrying conductors will reduce what each one can carry — see the bundling adjustment table.

Source: NFPA 70, National Electrical Code, Chapter 9, Table 1; NFPA 70, National Electrical Code, Chapter 9, Table 4; NFPA 70, National Electrical Code, Chapter 9, Table 5. Published by NFPA.NEC 2023