Reference tables · Conduit fill

RMC (rigid metal conduit)

2" RMC conduit fill capacity

2" RMC has an internal area of 3.408 in². At the 40% limit that applies to more than two conductors, it holds up to 102 12 AWG THHN conductors.

Capacity

Maximum conductors by size and insulation

ConductorTHHN / THWN-2XHHW-2THW
14 AWG1409865
12 AWG1027552
10 AWG645640
8 AWG373124
6 AWG262318
4 AWG161614
3 AWG141412
2 AWG111110
1 AWG887
1/0 AWG776
2/0 AWG665
3/0 AWG554
4/0 AWG443
250 kcmil332
300 kcmil232
350 kcmil221
400 kcmil111
500 kcmil111
600 kcmil111
700 kcmil111
750 kcmil111
Maximum number of same-size, same-insulation conductors in 2" RMC (3.408 in² internal). Counts above two use the 40% limit; a dash means not even one fits.

Fill limits

Internal area3.408 in²
One conductor53% — 1.8062 in²
Two conductors31% — 1.0565 in²
More than two40% — 1.3632 in²

Fitting is not the same as finishing

These counts are the mathematical fill limit, not a promise the pull will go well. A raceway at 39% fill with four 90° bends and a hundred feet between pull points is legal and miserable. Experienced installers routinely size up a trade size on long or bendy runs, and the material cost difference is usually smaller than the labour cost of a fight.

Two other things this table does not model. Nipples 24 inches and shorter between enclosures are permitted a much higher fill. And a mixed set of conductor sizes has to be summed by area rather than looked up by count — the conduit fill calculator handles that.

Remember also that conductor count drives ampacity derating separately. Filling this conduit with current-carrying conductors will reduce what each one can carry — see the bundling adjustment table.

Source: NFPA 70, National Electrical Code, Chapter 9, Table 1; NFPA 70, National Electrical Code, Chapter 9, Table 4; NFPA 70, National Electrical Code, Chapter 9, Table 5. Published by NFPA.NEC 2023

Related

Other sizes and types