Reference tables · Conduit fill

RMC (rigid metal conduit)

3" RMC conduit fill capacity

3" RMC has an internal area of 7.499 in². At the 40% limit that applies to more than two conductors, it holds up to 225 12 AWG THHN conductors.

Capacity

Maximum conductors by size and insulation

ConductorTHHN / THWN-2XHHW-2THW
14 AWG309215143
12 AWG225165115
10 AWG14212390
8 AWG816853
6 AWG595041
4 AWG363630
3 AWG303126
2 AWG252622
1 AWG191915
1/0 AWG161613
2/0 AWG131311
3/0 AWG11119
4/0 AWG998
250 kcmil776
300 kcmil665
350 kcmil555
400 kcmil554
500 kcmil443
600 kcmil333
700 kcmil332
750 kcmil221
Maximum number of same-size, same-insulation conductors in 3" RMC (7.499 in² internal). Counts above two use the 40% limit; a dash means not even one fits.

Fill limits

Internal area7.499 in²
One conductor53% — 3.9745 in²
Two conductors31% — 2.3247 in²
More than two40% — 2.9996 in²

Fitting is not the same as finishing

These counts are the mathematical fill limit, not a promise the pull will go well. A raceway at 39% fill with four 90° bends and a hundred feet between pull points is legal and miserable. Experienced installers routinely size up a trade size on long or bendy runs, and the material cost difference is usually smaller than the labour cost of a fight.

Two other things this table does not model. Nipples 24 inches and shorter between enclosures are permitted a much higher fill. And a mixed set of conductor sizes has to be summed by area rather than looked up by count — the conduit fill calculator handles that.

Remember also that conductor count drives ampacity derating separately. Filling this conduit with current-carrying conductors will reduce what each one can carry — see the bundling adjustment table.

Source: NFPA 70, National Electrical Code, Chapter 9, Table 1; NFPA 70, National Electrical Code, Chapter 9, Table 4; NFPA 70, National Electrical Code, Chapter 9, Table 5. Published by NFPA.NEC 2023

Related

Other sizes and types