Reference tables · Conduit fill

PVC Schedule 40

3" PVC Sch 40 conduit fill capacity

3" PVC Sch 40 has an internal area of 7.268 in². At the 40% limit that applies to more than two conductors, it holds up to 218 12 AWG THHN conductors.

Capacity

Maximum conductors by size and insulation

ConductorTHHN / THWN-2XHHW-2THW
14 AWG299209139
12 AWG218160111
10 AWG13711987
8 AWG796652
6 AWG574940
4 AWG353529
3 AWG293025
2 AWG252521
1 AWG181815
1/0 AWG151513
2/0 AWG131311
3/0 AWG10119
4/0 AWG897
250 kcmil776
300 kcmil665
350 kcmil554
400 kcmil454
500 kcmil443
600 kcmil332
700 kcmil222
750 kcmil221
Maximum number of same-size, same-insulation conductors in 3" PVC Sch 40 (7.268 in² internal). Counts above two use the 40% limit; a dash means not even one fits.

Fill limits

Internal area7.268 in²
One conductor53% — 3.8520 in²
Two conductors31% — 2.2531 in²
More than two40% — 2.9072 in²

Fitting is not the same as finishing

These counts are the mathematical fill limit, not a promise the pull will go well. A raceway at 39% fill with four 90° bends and a hundred feet between pull points is legal and miserable. Experienced installers routinely size up a trade size on long or bendy runs, and the material cost difference is usually smaller than the labour cost of a fight.

Two other things this table does not model. Nipples 24 inches and shorter between enclosures are permitted a much higher fill. And a mixed set of conductor sizes has to be summed by area rather than looked up by count — the conduit fill calculator handles that.

Remember also that conductor count drives ampacity derating separately. Filling this conduit with current-carrying conductors will reduce what each one can carry — see the bundling adjustment table.

Source: NFPA 70, National Electrical Code, Chapter 9, Table 1; NFPA 70, National Electrical Code, Chapter 9, Table 4; NFPA 70, National Electrical Code, Chapter 9, Table 5. Published by NFPA.NEC 2023