Reference tables · Conduit fill

PVC Schedule 40

1-1/2" PVC Sch 40 conduit fill capacity

1-1/2" PVC Sch 40 has an internal area of 1.986 in². At the 40% limit that applies to more than two conductors, it holds up to 59 12 AWG THHN conductors.

Capacity

Maximum conductors by size and insulation

ConductorTHHN / THWN-2XHHW-2THW
14 AWG815738
12 AWG594330
10 AWG373223
8 AWG211814
6 AWG151310
4 AWG998
3 AWG887
2 AWG665
1 AWG554
1/0 AWG443
2/0 AWG333
3/0 AWG231
4/0 AWG111
250 kcmil111
300 kcmil111
350 kcmil111
400 kcmil111
500 kcmil111
600 kcmil111
700 kcmil11
750 kcmil1
Maximum number of same-size, same-insulation conductors in 1-1/2" PVC Sch 40 (1.986 in² internal). Counts above two use the 40% limit; a dash means not even one fits.

Fill limits

Internal area1.986 in²
One conductor53% — 1.0526 in²
Two conductors31% — 0.6157 in²
More than two40% — 0.7944 in²

Fitting is not the same as finishing

These counts are the mathematical fill limit, not a promise the pull will go well. A raceway at 39% fill with four 90° bends and a hundred feet between pull points is legal and miserable. Experienced installers routinely size up a trade size on long or bendy runs, and the material cost difference is usually smaller than the labour cost of a fight.

Two other things this table does not model. Nipples 24 inches and shorter between enclosures are permitted a much higher fill. And a mixed set of conductor sizes has to be summed by area rather than looked up by count — the conduit fill calculator handles that.

Remember also that conductor count drives ampacity derating separately. Filling this conduit with current-carrying conductors will reduce what each one can carry — see the bundling adjustment table.

Source: NFPA 70, National Electrical Code, Chapter 9, Table 1; NFPA 70, National Electrical Code, Chapter 9, Table 4; NFPA 70, National Electrical Code, Chapter 9, Table 5. Published by NFPA.NEC 2023