EMT (electrical metallic tubing)

2-1/2" EMT conduit fill capacity

2-1/2" EMT has an internal area of 5.858 in². At the 40% limit that applies to more than two conductors, it holds up to 176 12 AWG THHN conductors.

Capacity

Maximum conductors by size and insulation

ConductorTHHN / THWN-2XHHW-2THW
14 AWG241168112
12 AWG17612990
10 AWG1119670
8 AWG645342
6 AWG463932
4 AWG282824
3 AWG242420
2 AWG202017
1 AWG151512
1/0 AWG121210
2/0 AWG10108
3/0 AWG887
4/0 AWG776
250 kcmil565
300 kcmil554
350 kcmil443
400 kcmil343
500 kcmil332
600 kcmil221
700 kcmil111
750 kcmil111
Maximum number of same-size, same-insulation conductors in 2-1/2" EMT (5.858 in² internal). Counts above two use the 40% limit; a dash means not even one fits.

Fill limits

Internal area5.858 in²
One conductor53% — 3.1047 in²
Two conductors31% — 1.8160 in²
More than two40% — 2.3432 in²

Fitting is not the same as finishing

These counts are the mathematical fill limit, not a promise the pull will go well. A raceway at 39% fill with four 90° bends and a hundred feet between pull points is legal and miserable. Experienced installers routinely size up a trade size on long or bendy runs, and the material cost difference is usually smaller than the labour cost of a fight.

Two other things this table does not model. Nipples 24 inches and shorter between enclosures are permitted a much higher fill. And a mixed set of conductor sizes has to be summed by area rather than looked up by count — the conduit fill calculator handles that.

Remember also that conductor count drives ampacity derating separately. Filling this conduit with current-carrying conductors will reduce what each one can carry — see the bundling adjustment table.

Source: NFPA 70, National Electrical Code, Chapter 9, Table 1; NFPA 70, National Electrical Code, Chapter 9, Table 4; NFPA 70, National Electrical Code, Chapter 9, Table 5. Published by NFPA.NEC 2023