Reference tables · Conduit fill

RMC (rigid metal conduit)

4" RMC conduit fill capacity

4" RMC has an internal area of 12.882 in². At the 40% limit that applies to more than two conductors, it holds up to 387 12 AWG THHN conductors.

Capacity

Maximum conductors by size and insulation

ConductorTHHN / THWN-2XHHW-2THW
14 AWG400370246
12 AWG387284198
10 AWG244212154
8 AWG14011792
6 AWG1018770
4 AWG626352
3 AWG525345
2 AWG444438
1 AWG323327
1/0 AWG272823
2/0 AWG232319
3/0 AWG191916
4/0 AWG151613
250 kcmil121311
300 kcmil11119
350 kcmil998
400 kcmil887
500 kcmil776
600 kcmil555
700 kcmil554
750 kcmil444
Maximum number of same-size, same-insulation conductors in 4" RMC (12.882 in² internal). Counts above two use the 40% limit; a dash means not even one fits.

Fill limits

Internal area12.882 in²
One conductor53% — 6.8275 in²
Two conductors31% — 3.9934 in²
More than two40% — 5.1528 in²

Fitting is not the same as finishing

These counts are the mathematical fill limit, not a promise the pull will go well. A raceway at 39% fill with four 90° bends and a hundred feet between pull points is legal and miserable. Experienced installers routinely size up a trade size on long or bendy runs, and the material cost difference is usually smaller than the labour cost of a fight.

Two other things this table does not model. Nipples 24 inches and shorter between enclosures are permitted a much higher fill. And a mixed set of conductor sizes has to be summed by area rather than looked up by count — the conduit fill calculator handles that.

Remember also that conductor count drives ampacity derating separately. Filling this conduit with current-carrying conductors will reduce what each one can carry — see the bundling adjustment table.

Source: NFPA 70, National Electrical Code, Chapter 9, Table 1; NFPA 70, National Electrical Code, Chapter 9, Table 4; NFPA 70, National Electrical Code, Chapter 9, Table 5. Published by NFPA.NEC 2023

Related

Other sizes and types