Reference tables · Conduit fill

EMT (electrical metallic tubing)

4" EMT conduit fill capacity

4" EMT has an internal area of 14.753 in². At the 40% limit that applies to more than two conductors, it holds up to 400 12 AWG THHN conductors.

Capacity

Maximum conductors by size and insulation

ConductorTHHN / THWN-2XHHW-2THW
14 AWG400400282
12 AWG400326226
10 AWG279242177
8 AWG161135106
6 AWG11610081
4 AWG717260
3 AWG606152
2 AWG505144
1 AWG373831
1/0 AWG313226
2/0 AWG262622
3/0 AWG222218
4/0 AWG181815
250 kcmil141512
300 kcmil121311
350 kcmil11119
400 kcmil10108
500 kcmil887
600 kcmil666
700 kcmil555
750 kcmil555
Maximum number of same-size, same-insulation conductors in 4" EMT (14.753 in² internal). Counts above two use the 40% limit; a dash means not even one fits.

Fill limits

Internal area14.753 in²
One conductor53% — 7.8191 in²
Two conductors31% — 4.5734 in²
More than two40% — 5.9012 in²

Fitting is not the same as finishing

These counts are the mathematical fill limit, not a promise the pull will go well. A raceway at 39% fill with four 90° bends and a hundred feet between pull points is legal and miserable. Experienced installers routinely size up a trade size on long or bendy runs, and the material cost difference is usually smaller than the labour cost of a fight.

Two other things this table does not model. Nipples 24 inches and shorter between enclosures are permitted a much higher fill. And a mixed set of conductor sizes has to be summed by area rather than looked up by count — the conduit fill calculator handles that.

Remember also that conductor count drives ampacity derating separately. Filling this conduit with current-carrying conductors will reduce what each one can carry — see the bundling adjustment table.

Source: NFPA 70, National Electrical Code, Chapter 9, Table 1; NFPA 70, National Electrical Code, Chapter 9, Table 4; NFPA 70, National Electrical Code, Chapter 9, Table 5. Published by NFPA.NEC 2023