Reference tables · Conduit fill

PVC Schedule 40

4" PVC Sch 40 conduit fill capacity

4" PVC Sch 40 has an internal area of 12.554 in². At the 40% limit that applies to more than two conductors, it holds up to 377 12 AWG THHN conductors.

Capacity

Maximum conductors by size and insulation

ConductorTHHN / THWN-2XHHW-2THW
14 AWG400361240
12 AWG377277193
10 AWG237206150
8 AWG13711490
6 AWG998569
4 AWG606151
3 AWG515244
2 AWG434337
1 AWG323226
1/0 AWG272722
2/0 AWG222219
3/0 AWG181916
4/0 AWG151513
250 kcmil121210
300 kcmil10119
350 kcmil998
400 kcmil887
500 kcmil776
600 kcmil555
700 kcmil554
750 kcmil444
Maximum number of same-size, same-insulation conductors in 4" PVC Sch 40 (12.554 in² internal). Counts above two use the 40% limit; a dash means not even one fits.

Fill limits

Internal area12.554 in²
One conductor53% — 6.6536 in²
Two conductors31% — 3.8917 in²
More than two40% — 5.0216 in²

Fitting is not the same as finishing

These counts are the mathematical fill limit, not a promise the pull will go well. A raceway at 39% fill with four 90° bends and a hundred feet between pull points is legal and miserable. Experienced installers routinely size up a trade size on long or bendy runs, and the material cost difference is usually smaller than the labour cost of a fight.

Two other things this table does not model. Nipples 24 inches and shorter between enclosures are permitted a much higher fill. And a mixed set of conductor sizes has to be summed by area rather than looked up by count — the conduit fill calculator handles that.

Remember also that conductor count drives ampacity derating separately. Filling this conduit with current-carrying conductors will reduce what each one can carry — see the bundling adjustment table.

Source: NFPA 70, National Electrical Code, Chapter 9, Table 1; NFPA 70, National Electrical Code, Chapter 9, Table 4; NFPA 70, National Electrical Code, Chapter 9, Table 5. Published by NFPA.NEC 2023