Reference tables · Copper ampacity

2023 NEC · Table 310.16

700 kcmil copper wire ampacity

At a 75°C termination rating, 700 kcmil copper carries 460 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.

700 kcmil700,000 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C385 A
75°C460 ATHW
90°C520 ATHHN / THWN-2, XHHW-2
700 kcmil copper, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 700 kcmil copper is used for

700 kcmil copper carries 460 A at 75°C. Conductors in the kcmil range are service, feeder, and distribution conductors, frequently run as paralleled sets under rules this reference does not model. It pairs with a 450 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 460 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C510.6 A408.5 A357.4 A255.3 A229.8 A
30°C460 A368 A322 A230 A207 A
40°C404.8 A323.8 A283.4 A202.4 A182.2 A
50°C345 A276 A241.5 A172.5 A155.3 A
700 kcmil copper at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils700,000
DC resistance0.0184 Ω per 1000 ft
Ampacity at 75°C460 A
Overcurrent ceilingSet by ampacity
Largest standard breaker450 A
Area, THHN / THWN-20.9887 in²
Area, XHHW-20.9923 in²
Area, THW1.101 in²

Voltage drop over distance

Single-phase 240 V, carrying 460 A on 700 kcmil copper.

One-way distanceDropWithin 3%?
25 ft0.18%Yes
50 ft0.35%Yes
100 ft0.71%Yes
150 ft1.06%Yes
200 ft1.41%Yes
300 ft2.12%Yes
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023