Reference tables · Aluminum ampacity

2023 NEC · Table 310.16

700 kcmil aluminum wire ampacity

At a 75°C termination rating, 700 kcmil aluminum carries 375 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.

700 kcmil700,000 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C315 A
75°C375 ATHW
90°C425 ATHHN / THWN-2, XHHW-2
700 kcmil aluminum, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 700 kcmil aluminum is used for

700 kcmil aluminum carries 375 A at 75°C. Conductors in the kcmil range are service, feeder, and distribution conductors, frequently run as paralleled sets under rules this reference does not model. It pairs with a 350 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 375 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C416.3 A333 A291.4 A208.1 A187.3 A
30°C375 A300 A262.5 A187.5 A168.8 A
40°C330 A264 A231 A165 A148.5 A
50°C281.3 A225 A196.9 A140.6 A126.6 A
700 kcmil aluminum at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils700,000
DC resistance0.0303 Ω per 1000 ft
Ampacity at 75°C375 A
Overcurrent ceilingSet by ampacity
Largest standard breaker350 A
Area, THHN / THWN-20.9887 in²
Area, XHHW-20.9923 in²
Area, THW1.101 in²

Voltage drop over distance

Single-phase 240 V, carrying 375 A on 700 kcmil aluminum.

One-way distanceDropWithin 3%?
25 ft0.24%Yes
50 ft0.47%Yes
100 ft0.95%Yes
150 ft1.42%Yes
200 ft1.89%Yes
300 ft2.84%Yes
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023