Reference tables · Copper ampacity

2023 NEC · Table 310.16

600 kcmil copper wire ampacity

At a 75°C termination rating, 600 kcmil copper carries 420 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.

600 kcmil600,000 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C350 A
75°C420 ATHW
90°C475 ATHHN / THWN-2, XHHW-2
600 kcmil copper, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 600 kcmil copper is used for

600 kcmil copper carries 420 A at 75°C. Conductors in the kcmil range are service, feeder, and distribution conductors, frequently run as paralleled sets under rules this reference does not model. It pairs with a 400 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 420 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C466.2 A373 A326.3 A233.1 A209.8 A
30°C420 A336 A294 A210 A189 A
40°C369.6 A295.7 A258.7 A184.8 A166.3 A
50°C315 A252 A220.5 A157.5 A141.8 A
600 kcmil copper at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils600,000
DC resistance0.0214 Ω per 1000 ft
Ampacity at 75°C420 A
Overcurrent ceilingSet by ampacity
Largest standard breaker400 A
Area, THHN / THWN-20.8676 in²
Area, XHHW-20.8709 in²
Area, THW0.9729 in²

Voltage drop over distance

Single-phase 240 V, carrying 420 A on 600 kcmil copper.

One-way distanceDropWithin 3%?
25 ft0.19%Yes
50 ft0.38%Yes
100 ft0.75%Yes
150 ft1.13%Yes
200 ft1.51%Yes
300 ft2.26%Yes
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023