Reference tables · Copper ampacity

2023 NEC · Table 310.16

750 kcmil copper wire ampacity

At a 75°C termination rating, 750 kcmil copper carries 475 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.

750 kcmil750,000 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C400 A
75°C475 ATHW
90°C535 ATHHN / THWN-2, XHHW-2
750 kcmil copper, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 750 kcmil copper is used for

750 kcmil copper carries 475 A at 75°C. Conductors in the kcmil range are service, feeder, and distribution conductors, frequently run as paralleled sets under rules this reference does not model. It pairs with a 450 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 475 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C527.3 A421.8 A369.1 A263.6 A237.3 A
30°C475 A380 A332.5 A237.5 A213.8 A
40°C418 A334.4 A292.6 A209 A188.1 A
50°C356.3 A285 A249.4 A178.1 A160.3 A
750 kcmil copper at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils750,000
DC resistance0.0171 Ω per 1000 ft
Ampacity at 75°C475 A
Overcurrent ceilingSet by ampacity
Largest standard breaker450 A
Area, THHN / THWN-21.0496 in²
Area, XHHW-21.0532 in²
Area, THW1.1652 in²

Voltage drop over distance

Single-phase 240 V, carrying 475 A on 750 kcmil copper.

One-way distanceDropWithin 3%?
25 ft0.17%Yes
50 ft0.34%Yes
100 ft0.68%Yes
150 ft1.02%Yes
200 ft1.36%Yes
300 ft2.04%Yes
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023

Related

Nearby conductors