Reference tables · Aluminum ampacity

2023 NEC · Table 310.16

600 kcmil aluminum wire ampacity

At a 75°C termination rating, 600 kcmil aluminum carries 340 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.

600 kcmil600,000 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C285 A
75°C340 ATHW
90°C385 ATHHN / THWN-2, XHHW-2
600 kcmil aluminum, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 600 kcmil aluminum is used for

600 kcmil aluminum carries 340 A at 75°C. Conductors in the kcmil range are service, feeder, and distribution conductors, frequently run as paralleled sets under rules this reference does not model. It pairs with a 300 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 340 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C377.4 A301.9 A264.2 A188.7 A169.8 A
30°C340 A272 A238 A170 A153 A
40°C299.2 A239.4 A209.4 A149.6 A134.6 A
50°C255 A204 A178.5 A127.5 A114.8 A
600 kcmil aluminum at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils600,000
DC resistance0.0353 Ω per 1000 ft
Ampacity at 75°C340 A
Overcurrent ceilingSet by ampacity
Largest standard breaker300 A
Area, THHN / THWN-20.8676 in²
Area, XHHW-20.8709 in²
Area, THW0.9729 in²

Voltage drop over distance

Single-phase 240 V, carrying 340 A on 600 kcmil aluminum.

One-way distanceDropWithin 3%?
25 ft0.25%Yes
50 ft0.50%Yes
100 ft1.00%Yes
150 ft1.50%Yes
200 ft2.00%Yes
300 ft3.00%No
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023

Related

Nearby conductors