Reference tables · Aluminum ampacity

2023 NEC · Table 310.16

750 kcmil aluminum wire ampacity

At a 75°C termination rating, 750 kcmil aluminum carries 385 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.

750 kcmil750,000 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C320 A
75°C385 ATHW
90°C435 ATHHN / THWN-2, XHHW-2
750 kcmil aluminum, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 750 kcmil aluminum is used for

750 kcmil aluminum carries 385 A at 75°C. Conductors in the kcmil range are service, feeder, and distribution conductors, frequently run as paralleled sets under rules this reference does not model. It pairs with a 350 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 385 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C427.4 A341.9 A299.1 A213.7 A192.3 A
30°C385 A308 A269.5 A192.5 A173.3 A
40°C338.8 A271 A237.2 A169.4 A152.5 A
50°C288.8 A231 A202.1 A144.4 A129.9 A
750 kcmil aluminum at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils750,000
DC resistance0.0282 Ω per 1000 ft
Ampacity at 75°C385 A
Overcurrent ceilingSet by ampacity
Largest standard breaker350 A
Area, THHN / THWN-21.0496 in²
Area, XHHW-21.0532 in²
Area, THW1.1652 in²

Voltage drop over distance

Single-phase 240 V, carrying 385 A on 750 kcmil aluminum.

One-way distanceDropWithin 3%?
25 ft0.23%Yes
50 ft0.45%Yes
100 ft0.91%Yes
150 ft1.36%Yes
200 ft1.81%Yes
300 ft2.72%Yes
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023