Reference tables · Aluminum ampacity

2023 NEC · Table 310.16

500 kcmil aluminum wire ampacity

At a 75°C termination rating, 500 kcmil aluminum carries 310 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.

500 kcmil500,000 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C260 A
75°C310 ATHW
90°C350 ATHHN / THWN-2, XHHW-2
500 kcmil aluminum, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 500 kcmil aluminum is used for

500 kcmil aluminum carries 310 A at 75°C. Conductors in the kcmil range are service, feeder, and distribution conductors, frequently run as paralleled sets under rules this reference does not model. It pairs with a 300 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 310 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C344.1 A275.3 A240.9 A172.1 A154.8 A
30°C310 A248 A217 A155 A139.5 A
40°C272.8 A218.2 A191 A136.4 A122.8 A
50°C232.5 A186 A162.8 A116.3 A104.6 A
500 kcmil aluminum at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils500,000
DC resistance0.0424 Ω per 1000 ft
Ampacity at 75°C310 A
Overcurrent ceilingSet by ampacity
Largest standard breaker300 A
Area, THHN / THWN-20.7073 in²
Area, XHHW-20.6984 in²
Area, THW0.7901 in²

Voltage drop over distance

Single-phase 240 V, carrying 310 A on 500 kcmil aluminum.

One-way distanceDropWithin 3%?
25 ft0.27%Yes
50 ft0.55%Yes
100 ft1.10%Yes
150 ft1.64%Yes
200 ft2.19%Yes
300 ft3.29%No
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023