Reference tables · Copper ampacity

2023 NEC · Table 310.16

350 kcmil copper wire ampacity

At a 75°C termination rating, 350 kcmil copper carries 310 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.

350 kcmil350,000 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C260 A
75°C310 ATHW
90°C350 ATHHN / THWN-2, XHHW-2
350 kcmil copper, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 350 kcmil copper is used for

350 kcmil copper carries 310 A at 75°C. Conductors in the kcmil range are service, feeder, and distribution conductors, frequently run as paralleled sets under rules this reference does not model. It pairs with a 300 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 310 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C344.1 A275.3 A240.9 A172.1 A154.8 A
30°C310 A248 A217 A155 A139.5 A
40°C272.8 A218.2 A191 A136.4 A122.8 A
50°C232.5 A186 A162.8 A116.3 A104.6 A
350 kcmil copper at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils350,000
DC resistance0.0367 Ω per 1000 ft
Ampacity at 75°C310 A
Overcurrent ceilingSet by ampacity
Largest standard breaker300 A
Area, THHN / THWN-20.5242 in²
Area, XHHW-20.5166 in²
Area, THW0.5958 in²

Voltage drop over distance

Single-phase 240 V, carrying 310 A on 350 kcmil copper.

One-way distanceDropWithin 3%?
25 ft0.24%Yes
50 ft0.48%Yes
100 ft0.95%Yes
150 ft1.43%Yes
200 ft1.90%Yes
300 ft2.86%Yes
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023