Reference tables · Copper ampacity

2023 NEC · Table 310.16

300 kcmil copper wire ampacity

At a 75°C termination rating, 300 kcmil copper carries 285 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.

300 kcmil300,000 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C240 A
75°C285 ATHW
90°C320 ATHHN / THWN-2, XHHW-2
300 kcmil copper, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 300 kcmil copper is used for

300 kcmil copper carries 285 A at 75°C. Conductors in the kcmil range are service, feeder, and distribution conductors, frequently run as paralleled sets under rules this reference does not model. It pairs with a 250 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 285 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C316.4 A253.1 A221.4 A158.2 A142.4 A
30°C285 A228 A199.5 A142.5 A128.3 A
40°C250.8 A200.6 A175.6 A125.4 A112.9 A
50°C213.8 A171 A149.6 A106.9 A96.2 A
300 kcmil copper at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils300,000
DC resistance0.0429 Ω per 1000 ft
Ampacity at 75°C285 A
Overcurrent ceilingSet by ampacity
Largest standard breaker250 A
Area, THHN / THWN-20.4608 in²
Area, XHHW-20.4536 in²
Area, THW0.5281 in²

Voltage drop over distance

Single-phase 240 V, carrying 285 A on 300 kcmil copper.

One-way distanceDropWithin 3%?
25 ft0.26%Yes
50 ft0.51%Yes
100 ft1.02%Yes
150 ft1.53%Yes
200 ft2.04%Yes
300 ft3.06%No
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023

Related

Nearby conductors