Reference tables · Aluminum ampacity

2023 NEC · Table 310.16

350 kcmil aluminum wire ampacity

At a 75°C termination rating, 350 kcmil aluminum carries 250 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.

350 kcmil350,000 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C210 A
75°C250 ATHW
90°C280 ATHHN / THWN-2, XHHW-2
350 kcmil aluminum, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 350 kcmil aluminum is used for

350 kcmil aluminum carries 250 A at 75°C. Conductors in the kcmil range are service, feeder, and distribution conductors, frequently run as paralleled sets under rules this reference does not model. It pairs with a 250 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 250 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C277.5 A222 A194.3 A138.8 A124.9 A
30°C250 A200 A175 A125 A112.5 A
40°C220 A176 A154 A110 A99 A
50°C187.5 A150 A131.3 A93.8 A84.4 A
350 kcmil aluminum at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils350,000
DC resistance0.0605 Ω per 1000 ft
Ampacity at 75°C250 A
Overcurrent ceilingSet by ampacity
Largest standard breaker250 A
Area, THHN / THWN-20.5242 in²
Area, XHHW-20.5166 in²
Area, THW0.5958 in²

Voltage drop over distance

Single-phase 240 V, carrying 250 A on 350 kcmil aluminum.

One-way distanceDropWithin 3%?
25 ft0.32%Yes
50 ft0.63%Yes
100 ft1.26%Yes
150 ft1.89%Yes
200 ft2.52%Yes
300 ft3.79%No
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023