Reference tables · Copper ampacity

2023 NEC · Table 310.16

3/0 AWG copper wire ampacity

At a 75°C termination rating, 3/0 AWG copper carries 200 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.

3/0 AWG167,800 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C165 A
75°C200 ATHW
90°C225 ATHHN / THWN-2, XHHW-2
3/0 AWG copper, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 3/0 AWG copper is used for

3/0 AWG copper carries 200 A at 75°C. Conductors this size are service entrance and main feeder conductors — the run between a meter and a panel, or between a main panel and a large subpanel. It pairs with a 200 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 200 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C222 A177.6 A155.4 A111 A99.9 A
30°C200 A160 A140 A100 A90 A
40°C176 A140.8 A123.2 A88 A79.2 A
50°C150 A120 A105 A75 A67.5 A
3/0 AWG copper at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils167,800
DC resistance0.0766 Ω per 1000 ft
Ampacity at 75°C200 A
Overcurrent ceilingSet by ampacity
Largest standard breaker200 A
Area, THHN / THWN-20.2679 in²
Area, XHHW-20.2642 in²
Area, THW0.3117 in²

Voltage drop over distance

Single-phase 240 V, carrying 200 A on 3/0 AWG copper.

One-way distanceDropWithin 3%?
25 ft0.32%Yes
50 ft0.64%Yes
100 ft1.28%Yes
150 ft1.92%Yes
200 ft2.56%Yes
300 ft3.84%No
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023