Reference tables · Aluminum ampacity

2023 NEC · Table 310.16

3/0 AWG aluminum wire ampacity

At a 75°C termination rating, 3/0 AWG aluminum carries 155 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.

3/0 AWG167,800 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C130 A
75°C155 ATHW
90°C175 ATHHN / THWN-2, XHHW-2
3/0 AWG aluminum, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 3/0 AWG aluminum is used for

3/0 AWG aluminum carries 155 A at 75°C. Conductors this size are service entrance and main feeder conductors — the run between a meter and a panel, or between a main panel and a large subpanel. It pairs with a 150 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 155 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C172.1 A137.6 A120.4 A86 A77.4 A
30°C155 A124 A108.5 A77.5 A69.8 A
40°C136.4 A109.1 A95.5 A68.2 A61.4 A
50°C116.3 A93 A81.4 A58.1 A52.3 A
3/0 AWG aluminum at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils167,800
DC resistance0.126 Ω per 1000 ft
Ampacity at 75°C155 A
Overcurrent ceilingSet by ampacity
Largest standard breaker150 A
Area, THHN / THWN-20.2679 in²
Area, XHHW-20.2642 in²
Area, THW0.3117 in²

Voltage drop over distance

Single-phase 240 V, carrying 155 A on 3/0 AWG aluminum.

One-way distanceDropWithin 3%?
25 ft0.41%Yes
50 ft0.82%Yes
100 ft1.63%Yes
150 ft2.45%Yes
200 ft3.26%No
300 ft4.90%No
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023

Related

Nearby conductors