Ampacity by temperature rating
| Temperature rating | Ampacity | Typical insulation |
|---|---|---|
| 60°C | 145 A | — |
| 75°C | 175 A | THW |
| 90°C | 195 A | THHN / THWN-2, XHHW-2 |
Reference tables · Copper ampacity
2023 NEC · Table 310.16
At a 75°C termination rating, 2/0 AWG copper carries 175 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.
| Temperature rating | Ampacity | Typical insulation |
|---|---|---|
| 60°C | 145 A | — |
| 75°C | 175 A | THW |
| 90°C | 195 A | THHN / THWN-2, XHHW-2 |
2/0 AWG copper carries 175 A at 75°C. Conductors this size are service entrance and main feeder conductors — the run between a meter and a panel, or between a main panel and a large subpanel. It pairs with a 175 A overcurrent device.
Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 175 A column at the terminals. Check the equipment's listing rather than assuming.
Derating
| Ambient | 3 conductors | 4 conductors | 7 conductors | 10 conductors | 21 conductors |
|---|---|---|---|---|---|
| 20°C | 194.3 A | 155.4 A | 136 A | 97.1 A | 87.4 A |
| 30°C | 175 A | 140 A | 122.5 A | 87.5 A | 78.8 A |
| 40°C | 154 A | 123.2 A | 107.8 A | 77 A | 69.3 A |
| 50°C | 131.3 A | 105 A | 91.9 A | 65.6 A | 59.1 A |
| Circular mils | 133,100 |
|---|---|
| DC resistance | 0.0967 Ω per 1000 ft |
| Ampacity at 75°C | 175 A |
| Overcurrent ceiling | Set by ampacity |
| Largest standard breaker | 175 A |
| Area, THHN / THWN-2 | 0.2223 in² |
| Area, XHHW-2 | 0.219 in² |
| Area, THW | 0.2624 in² |
Single-phase 240 V, carrying 175 A on 2/0 AWG copper.
| One-way distance | Drop | Within 3%? |
|---|---|---|
| 25 ft | 0.35% | Yes |
| 50 ft | 0.71% | Yes |
| 100 ft | 1.41% | Yes |
| 150 ft | 2.12% | Yes |
| 200 ft | 2.83% | Yes |
| 300 ft | 4.24% | No |
Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023
Related