Reference tables · Aluminum ampacity

2023 NEC · Table 310.16

2/0 AWG aluminum wire ampacity

At a 75°C termination rating, 2/0 AWG aluminum carries 135 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.

2/0 AWG133,100 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C115 A
75°C135 ATHW
90°C150 ATHHN / THWN-2, XHHW-2
2/0 AWG aluminum, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 2/0 AWG aluminum is used for

2/0 AWG aluminum carries 135 A at 75°C. Conductors this size are service entrance and main feeder conductors — the run between a meter and a panel, or between a main panel and a large subpanel. It pairs with a 125 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 135 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C149.9 A119.9 A104.9 A74.9 A67.4 A
30°C135 A108 A94.5 A67.5 A60.8 A
40°C118.8 A95 A83.2 A59.4 A53.5 A
50°C101.3 A81 A70.9 A50.6 A45.6 A
2/0 AWG aluminum at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils133,100
DC resistance0.159 Ω per 1000 ft
Ampacity at 75°C135 A
Overcurrent ceilingSet by ampacity
Largest standard breaker125 A
Area, THHN / THWN-20.2223 in²
Area, XHHW-20.219 in²
Area, THW0.2624 in²

Voltage drop over distance

Single-phase 240 V, carrying 135 A on 2/0 AWG aluminum.

One-way distanceDropWithin 3%?
25 ft0.45%Yes
50 ft0.90%Yes
100 ft1.79%Yes
150 ft2.69%Yes
200 ft3.58%No
300 ft5.38%No
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023