Reference tables · Copper ampacity

2023 NEC · Table 310.16

10 AWG copper wire ampacity

At a 75°C termination rating, 10 AWG copper carries 35 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors. Overcurrent protection is separately capped at 30 A by the small-conductor rule.

10 AWG10,380 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C30 A
75°C35 ATHW
90°C40 ATHHN / THWN-2, XHHW-2
10 AWG copper, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 10 AWG copper is used for

10 AWG copper is the standard conductor for 30 A circuits — electric water heaters, small subpanels, dryers on older installations, and window air conditioners. It carries 30 A and pairs with a 30 A overcurrent device.

Note the gap between the table and the ceiling. The 90°C column reads 40 A, but a 10 AWG copper conductor cannot be protected above 30 A regardless — the small-conductor rule sets that ceiling independently of ampacity. The higher table value exists so the conductor has headroom to be derated from, not so it can be put on a larger breaker.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 35 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C30 A30 A27.2 A19.4 A17.5 A
30°C30 A28 A24.5 A17.5 A15.8 A
40°C30 A24.6 A21.6 A15.4 A13.9 A
50°C26.3 A21 A18.4 A13.1 A11.8 A
10 AWG copper at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils10,380
DC resistance1.24 Ω per 1000 ft
Ampacity at 75°C35 A
Overcurrent ceiling30 A (small-conductor rule)
Largest standard breaker30 A
Area, THHN / THWN-20.0211 in²
Area, XHHW-20.0243 in²
Area, THW0.0333 in²

Voltage drop over distance

Single-phase 240 V, carrying 30 A on 10 AWG copper.

One-way distanceDropWithin 3%?
25 ft0.78%Yes
50 ft1.55%Yes
100 ft3.11%No
150 ft4.66%No
200 ft6.21%No
300 ft9.32%No
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023

Related

Nearby conductors