Reference tables · Aluminum ampacity

2023 NEC · Table 310.16

10 AWG aluminum wire ampacity

At a 75°C termination rating, 10 AWG aluminum carries 30 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors. Overcurrent protection is separately capped at 25 A by the small-conductor rule.

10 AWG10,380 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C25 A
75°C30 ATHW
90°C35 ATHHN / THWN-2, XHHW-2
10 AWG aluminum, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 10 AWG aluminum is used for

10 AWG aluminum is capped at 25 A by the small-conductor rule, which places it between the common 20 A and 30 A circuit sizes and makes it an awkward fit for most branch work.

Note the gap between the table and the ceiling. The 90°C column reads 35 A, but a 10 AWG aluminum conductor cannot be protected above 25 A regardless — the small-conductor rule sets that ceiling independently of ampacity. The higher table value exists so the conductor has headroom to be derated from, not so it can be put on a larger breaker.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 30 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C25 A25 A23.3 A16.7 A15 A
30°C25 A24 A21 A15 A13.5 A
40°C25 A21.1 A18.5 A13.2 A11.9 A
50°C22.5 A18 A15.7 A11.3 A10.1 A
10 AWG aluminum at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils10,380
DC resistance2.04 Ω per 1000 ft
Ampacity at 75°C30 A
Overcurrent ceiling25 A (small-conductor rule)
Largest standard breaker25 A
Area, THHN / THWN-20.0211 in²
Area, XHHW-20.0243 in²
Area, THW0.0333 in²

Voltage drop over distance

Single-phase 240 V, carrying 25 A on 10 AWG aluminum.

One-way distanceDropWithin 3%?
25 ft1.06%Yes
50 ft2.13%Yes
100 ft4.25%No
150 ft6.38%No
200 ft8.51%No
300 ft12.76%No
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023