Reference tables · Copper ampacity

2023 NEC · Table 310.16

8 AWG copper wire ampacity

At a 75°C termination rating, 8 AWG copper carries 50 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.

8 AWG16,510 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C40 A
75°C50 ATHW
90°C55 ATHHN / THWN-2, XHHW-2
8 AWG copper, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 8 AWG copper is used for

8 AWG copper carries 50 A at 75°C, making it a common choice for 40 A and 50 A circuits — ranges, larger water heaters, EV charging equipment, and hot tubs. It typically pairs with a 50 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 50 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C55.5 A44.4 A38.9 A27.8 A25 A
30°C50 A40 A35 A25 A22.5 A
40°C44 A35.2 A30.8 A22 A19.8 A
50°C37.5 A30 A26.3 A18.8 A16.9 A
8 AWG copper at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils16,510
DC resistance0.778 Ω per 1000 ft
Ampacity at 75°C50 A
Overcurrent ceilingSet by ampacity
Largest standard breaker50 A
Area, THHN / THWN-20.0366 in²
Area, XHHW-20.0437 in²
Area, THW0.0556 in²

Voltage drop over distance

Single-phase 240 V, carrying 50 A on 8 AWG copper.

One-way distanceDropWithin 3%?
25 ft0.81%Yes
50 ft1.63%Yes
100 ft3.26%No
150 ft4.88%No
200 ft6.51%No
300 ft9.77%No
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023

Related

Nearby conductors