Reference tables · Copper ampacity

2023 NEC · Table 310.16

12 AWG copper wire ampacity

At a 75°C termination rating, 12 AWG copper carries 25 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors. Overcurrent protection is separately capped at 20 A by the small-conductor rule.

12 AWG6,530 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C20 A
75°C25 ATHW
90°C30 ATHHN / THWN-2, XHHW-2
12 AWG copper, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 12 AWG copper is used for

12 AWG copper is the workhorse of 20 A branch circuits — receptacles, kitchen small-appliance circuits, and general-purpose power. It pairs with a 20 A breaker and is the smallest conductor most jurisdictions accept for receptacle circuits in a kitchen or garage.

Note the gap between the table and the ceiling. The 90°C column reads 30 A, but a 12 AWG copper conductor cannot be protected above 20 A regardless — the small-conductor rule sets that ceiling independently of ampacity. The higher table value exists so the conductor has headroom to be derated from, not so it can be put on a larger breaker.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 25 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C20 A20 A19.4 A13.9 A12.5 A
30°C20 A20 A17.5 A12.5 A11.3 A
40°C20 A17.6 A15.4 A11 A9.9 A
50°C18.8 A15 A13.1 A9.4 A8.4 A
12 AWG copper at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils6,530
DC resistance1.98 Ω per 1000 ft
Ampacity at 75°C25 A
Overcurrent ceiling20 A (small-conductor rule)
Largest standard breaker20 A
Area, THHN / THWN-20.0133 in²
Area, XHHW-20.0181 in²
Area, THW0.026 in²

Voltage drop over distance

Single-phase 240 V, carrying 20 A on 12 AWG copper.

One-way distanceDropWithin 3%?
25 ft0.82%Yes
50 ft1.65%Yes
100 ft3.29%No
150 ft4.94%No
200 ft6.58%No
300 ft9.88%No
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023

Related

Nearby conductors