Reference tables · Aluminum ampacity

2023 NEC · Table 310.16

12 AWG aluminum wire ampacity

At a 75°C termination rating, 12 AWG aluminum carries 20 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors. Overcurrent protection is separately capped at 15 A by the small-conductor rule.

12 AWG6,530 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C15 A
75°C20 ATHW
90°C25 ATHHN / THWN-2, XHHW-2
12 AWG aluminum, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 12 AWG aluminum is used for

12 AWG aluminum is limited to 15 A by the small-conductor rule, which makes it an unusual choice for branch circuits. Aluminum is normally reserved for larger feeders where the cost saving is meaningful.

Note the gap between the table and the ceiling. The 90°C column reads 25 A, but a 12 AWG aluminum conductor cannot be protected above 15 A regardless — the small-conductor rule sets that ceiling independently of ampacity. The higher table value exists so the conductor has headroom to be derated from, not so it can be put on a larger breaker.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 20 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C15 A15 A15 A11.1 A10 A
30°C15 A15 A14 A10 A9 A
40°C15 A14.1 A12.3 A8.8 A7.9 A
50°C15 A12 A10.5 A7.5 A6.8 A
12 AWG aluminum at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils6,530
DC resistance3.25 Ω per 1000 ft
Ampacity at 75°C20 A
Overcurrent ceiling15 A (small-conductor rule)
Largest standard breaker15 A
Area, THHN / THWN-20.0133 in²
Area, XHHW-20.0181 in²
Area, THW0.026 in²

Voltage drop over distance

Single-phase 240 V, carrying 15 A on 12 AWG aluminum.

One-way distanceDropWithin 3%?
25 ft1.01%Yes
50 ft2.03%Yes
100 ft4.06%No
150 ft6.09%No
200 ft8.12%No
300 ft12.17%No
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023