Reference tables · Aluminum ampacity

2023 NEC · Table 310.16

8 AWG aluminum wire ampacity

At a 75°C termination rating, 8 AWG aluminum carries 40 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.

8 AWG16,510 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C35 A
75°C40 ATHW
90°C45 ATHHN / THWN-2, XHHW-2
8 AWG aluminum, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 8 AWG aluminum is used for

8 AWG aluminum carries 40 A at 75°C, making it a common choice for 40 A and 50 A circuits — ranges, larger water heaters, EV charging equipment, and hot tubs. It typically pairs with a 40 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 40 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C44.4 A35.5 A31.1 A22.2 A20 A
30°C40 A32 A28 A20 A18 A
40°C35.2 A28.2 A24.6 A17.6 A15.8 A
50°C30 A24 A21 A15 A13.5 A
8 AWG aluminum at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils16,510
DC resistance1.28 Ω per 1000 ft
Ampacity at 75°C40 A
Overcurrent ceilingSet by ampacity
Largest standard breaker40 A
Area, THHN / THWN-20.0366 in²
Area, XHHW-20.0437 in²
Area, THW0.0556 in²

Voltage drop over distance

Single-phase 240 V, carrying 40 A on 8 AWG aluminum.

One-way distanceDropWithin 3%?
25 ft1.07%Yes
50 ft2.14%Yes
100 ft4.28%No
150 ft6.42%No
200 ft8.56%No
300 ft12.84%No
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023

Related

Nearby conductors