1 AWG aluminum wire ampacity

At a 75°C termination rating, 1 AWG aluminum carries 100 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.

1 AWG83,690 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C85 A
75°C100 ATHW
90°C115 ATHHN / THWN-2, XHHW-2
1 AWG aluminum, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 1 AWG aluminum is used for

1 AWG aluminum carries 100 A at 75°C. Conductors in the kcmil range are service, feeder, and distribution conductors, frequently run as paralleled sets under rules this reference does not model. It pairs with a 100 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 100 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C111 A88.8 A77.7 A55.5 A50 A
30°C100 A80 A70 A50 A45 A
40°C88 A70.4 A61.6 A44 A39.6 A
50°C75 A60 A52.5 A37.5 A33.8 A
1 AWG aluminum at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils83,690
DC resistance0.253 Ω per 1000 ft
Ampacity at 75°C100 A
Overcurrent ceilingSet by ampacity
Largest standard breaker100 A
Area, THHN / THWN-20.1562 in²
Area, XHHW-20.1534 in²
Area, THW0.1901 in²

Voltage drop over distance

Single-phase 240 V, carrying 100 A on 1 AWG aluminum.

One-way distanceDropWithin 3%?
25 ft0.53%Yes
50 ft1.06%Yes
100 ft2.11%Yes
150 ft3.17%No
200 ft4.22%No
300 ft6.33%No
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.