Reference tables · Aluminum ampacity

2023 NEC · Table 310.16

2 AWG aluminum wire ampacity

At a 75°C termination rating, 2 AWG aluminum carries 90 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.

2 AWG66,360 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C75 A
75°C90 ATHW
90°C100 ATHHN / THWN-2, XHHW-2
2 AWG aluminum, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 2 AWG aluminum is used for

2 AWG aluminum carries 90 A at 75°C, putting it in feeder and subpanel territory — detached garages, workshops, and service upgrades. It pairs with a 90 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 90 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C99.9 A79.9 A69.9 A50 A45 A
30°C90 A72 A63 A45 A40.5 A
40°C79.2 A63.4 A55.4 A39.6 A35.6 A
50°C67.5 A54 A47.3 A33.8 A30.4 A
2 AWG aluminum at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils66,360
DC resistance0.319 Ω per 1000 ft
Ampacity at 75°C90 A
Overcurrent ceilingSet by ampacity
Largest standard breaker90 A
Area, THHN / THWN-20.1158 in²
Area, XHHW-20.1146 in²
Area, THW0.1333 in²

Voltage drop over distance

Single-phase 240 V, carrying 90 A on 2 AWG aluminum.

One-way distanceDropWithin 3%?
25 ft0.60%Yes
50 ft1.20%Yes
100 ft2.40%Yes
150 ft3.59%No
200 ft4.79%No
300 ft7.19%No
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023