Ampacity by temperature rating
| Temperature rating | Ampacity | Typical insulation |
|---|---|---|
| 60°C | 110 A | — |
| 75°C | 130 A | THW |
| 90°C | 145 A | THHN / THWN-2, XHHW-2 |
Reference tables · Copper ampacity
2023 NEC · Table 310.16
At a 75°C termination rating, 1 AWG copper carries 130 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.
| Temperature rating | Ampacity | Typical insulation |
|---|---|---|
| 60°C | 110 A | — |
| 75°C | 130 A | THW |
| 90°C | 145 A | THHN / THWN-2, XHHW-2 |
1 AWG copper carries 130 A at 75°C. Conductors in the kcmil range are service, feeder, and distribution conductors, frequently run as paralleled sets under rules this reference does not model. It pairs with a 125 A overcurrent device.
Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 130 A column at the terminals. Check the equipment's listing rather than assuming.
Derating
| Ambient | 3 conductors | 4 conductors | 7 conductors | 10 conductors | 21 conductors |
|---|---|---|---|---|---|
| 20°C | 144.3 A | 115.4 A | 101 A | 72.2 A | 64.9 A |
| 30°C | 130 A | 104 A | 91 A | 65 A | 58.5 A |
| 40°C | 114.4 A | 91.5 A | 80.1 A | 57.2 A | 51.5 A |
| 50°C | 97.5 A | 78 A | 68.3 A | 48.8 A | 43.9 A |
| Circular mils | 83,690 |
|---|---|
| DC resistance | 0.154 Ω per 1000 ft |
| Ampacity at 75°C | 130 A |
| Overcurrent ceiling | Set by ampacity |
| Largest standard breaker | 125 A |
| Area, THHN / THWN-2 | 0.1562 in² |
| Area, XHHW-2 | 0.1534 in² |
| Area, THW | 0.1901 in² |
Single-phase 240 V, carrying 130 A on 1 AWG copper.
| One-way distance | Drop | Within 3%? |
|---|---|---|
| 25 ft | 0.42% | Yes |
| 50 ft | 0.83% | Yes |
| 100 ft | 1.67% | Yes |
| 150 ft | 2.50% | Yes |
| 200 ft | 3.34% | No |
| 300 ft | 5.01% | No |
Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023
Related