Reference tables · Copper ampacity

2023 NEC · Table 310.16

1 AWG copper wire ampacity

At a 75°C termination rating, 1 AWG copper carries 130 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.

1 AWG83,690 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C110 A
75°C130 ATHW
90°C145 ATHHN / THWN-2, XHHW-2
1 AWG copper, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 1 AWG copper is used for

1 AWG copper carries 130 A at 75°C. Conductors in the kcmil range are service, feeder, and distribution conductors, frequently run as paralleled sets under rules this reference does not model. It pairs with a 125 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 130 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C144.3 A115.4 A101 A72.2 A64.9 A
30°C130 A104 A91 A65 A58.5 A
40°C114.4 A91.5 A80.1 A57.2 A51.5 A
50°C97.5 A78 A68.3 A48.8 A43.9 A
1 AWG copper at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils83,690
DC resistance0.154 Ω per 1000 ft
Ampacity at 75°C130 A
Overcurrent ceilingSet by ampacity
Largest standard breaker125 A
Area, THHN / THWN-20.1562 in²
Area, XHHW-20.1534 in²
Area, THW0.1901 in²

Voltage drop over distance

Single-phase 240 V, carrying 130 A on 1 AWG copper.

One-way distanceDropWithin 3%?
25 ft0.42%Yes
50 ft0.83%Yes
100 ft1.67%Yes
150 ft2.50%Yes
200 ft3.34%No
300 ft5.01%No
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023

Related

Nearby conductors