Reference tables · Aluminum ampacity

2023 NEC · Table 310.16

4 AWG aluminum wire ampacity

At a 75°C termination rating, 4 AWG aluminum carries 65 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.

4 AWG41,740 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C55 A
75°C65 ATHW
90°C75 ATHHN / THWN-2, XHHW-2
4 AWG aluminum, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 4 AWG aluminum is used for

4 AWG aluminum carries 65 A at 75°C, putting it in feeder and subpanel territory — detached garages, workshops, and service upgrades. It pairs with a 60 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 65 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C72.2 A57.7 A50.5 A36.1 A32.5 A
30°C65 A52 A45.5 A32.5 A29.3 A
40°C57.2 A45.8 A40 A28.6 A25.7 A
50°C48.8 A39 A34.1 A24.4 A21.9 A
4 AWG aluminum at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils41,740
DC resistance0.508 Ω per 1000 ft
Ampacity at 75°C65 A
Overcurrent ceilingSet by ampacity
Largest standard breaker60 A
Area, THHN / THWN-20.0824 in²
Area, XHHW-20.0814 in²
Area, THW0.0973 in²

Voltage drop over distance

Single-phase 240 V, carrying 65 A on 4 AWG aluminum.

One-way distanceDropWithin 3%?
25 ft0.69%Yes
50 ft1.38%Yes
100 ft2.75%Yes
150 ft4.13%No
200 ft5.50%No
300 ft8.25%No
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.