Reference tables · Aluminum ampacity

2023 NEC · Table 310.16

3 AWG aluminum wire ampacity

At a 75°C termination rating, 3 AWG aluminum carries 75 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.

3 AWG52,620 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C65 A
75°C75 ATHW
90°C85 ATHHN / THWN-2, XHHW-2
3 AWG aluminum, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 3 AWG aluminum is used for

3 AWG aluminum carries 75 A at 75°C, putting it in feeder and subpanel territory — detached garages, workshops, and service upgrades. It pairs with a 70 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 75 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C83.3 A66.6 A58.3 A41.6 A37.5 A
30°C75 A60 A52.5 A37.5 A33.8 A
40°C66 A52.8 A46.2 A33 A29.7 A
50°C56.3 A45 A39.4 A28.1 A25.3 A
3 AWG aluminum at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils52,620
DC resistance0.403 Ω per 1000 ft
Ampacity at 75°C75 A
Overcurrent ceilingSet by ampacity
Largest standard breaker70 A
Area, THHN / THWN-20.0973 in²
Area, XHHW-20.0962 in²
Area, THW0.1134 in²

Voltage drop over distance

Single-phase 240 V, carrying 75 A on 3 AWG aluminum.

One-way distanceDropWithin 3%?
25 ft0.63%Yes
50 ft1.26%Yes
100 ft2.52%Yes
150 ft3.78%No
200 ft5.04%No
300 ft7.55%No
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023