Reference tables · Copper ampacity

2023 NEC · Table 310.16

4 AWG copper wire ampacity

At a 75°C termination rating, 4 AWG copper carries 85 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.

4 AWG41,740 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C70 A
75°C85 ATHW
90°C95 ATHHN / THWN-2, XHHW-2
4 AWG copper, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 4 AWG copper is used for

4 AWG copper carries 85 A at 75°C, putting it in feeder and subpanel territory — detached garages, workshops, and service upgrades. It pairs with a 80 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 85 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C94.4 A75.5 A66 A47.2 A42.5 A
30°C85 A68 A59.5 A42.5 A38.3 A
40°C74.8 A59.8 A52.4 A37.4 A33.7 A
50°C63.8 A51 A44.6 A31.9 A28.7 A
4 AWG copper at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils41,740
DC resistance0.308 Ω per 1000 ft
Ampacity at 75°C85 A
Overcurrent ceilingSet by ampacity
Largest standard breaker80 A
Area, THHN / THWN-20.0824 in²
Area, XHHW-20.0814 in²
Area, THW0.0973 in²

Voltage drop over distance

Single-phase 240 V, carrying 85 A on 4 AWG copper.

One-way distanceDropWithin 3%?
25 ft0.55%Yes
50 ft1.09%Yes
100 ft2.19%Yes
150 ft3.28%No
200 ft4.38%No
300 ft6.57%No
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023

Related

Nearby conductors