Reference tables · Aluminum ampacity

2023 NEC · Table 310.16

250 kcmil aluminum wire ampacity

At a 75°C termination rating, 250 kcmil aluminum carries 205 A under the published table's basis conditions — 30°C ambient, no more than three current-carrying conductors.

250 kcmil250,000 cmil

Ampacity by temperature rating

Temperature ratingAmpacityTypical insulation
60°C170 A
75°C205 ATHW
90°C230 ATHHN / THWN-2, XHHW-2
250 kcmil aluminum, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.

What 250 kcmil aluminum is used for

250 kcmil aluminum carries 205 A at 75°C. Conductors in the kcmil range are service, feeder, and distribution conductors, frequently run as paralleled sets under rules this reference does not model. It pairs with a 200 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 205 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C227.6 A182 A159.3 A113.8 A102.4 A
30°C205 A164 A143.5 A102.5 A92.3 A
40°C180.4 A144.3 A126.3 A90.2 A81.2 A
50°C153.8 A123 A107.6 A76.9 A69.2 A
250 kcmil aluminum at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4–6 → 80%, 7–9 → 70%, 10–20 → 50%.

Properties

Circular mils250,000
DC resistance0.0847 Ω per 1000 ft
Ampacity at 75°C205 A
Overcurrent ceilingSet by ampacity
Largest standard breaker200 A
Area, THHN / THWN-20.397 in²
Area, XHHW-20.3904 in²
Area, THW0.4596 in²

Voltage drop over distance

Single-phase 240 V, carrying 205 A on 250 kcmil aluminum.

One-way distanceDropWithin 3%?
25 ft0.36%Yes
50 ft0.72%Yes
100 ft1.45%Yes
150 ft2.17%Yes
200 ft2.90%Yes
300 ft4.35%No
Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023

Related

Nearby conductors